DNP3 Master
Review the following information for setting up and configuring the DNP3 Master driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Ethernet |
Validated devices/series | DNP3-compatible outstations |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, use software on your computer to configure the device for Ethernet access.
Caution: Make sure that the value you enter for Master Address is unique.
Parameter | Value |
---|---|
Type | DNP3 |
Driver | DNP3 Master |
Network Address | The device address you defined in Step 1 |
Network Port | 20000 |
Master Address | 0 |
Outstation Address | 1 |
Name | Value Types | Access Types | Min Address | Max Address | Description |
---|---|---|---|---|---|
G0 | ATTRIBUTE | R/W | 0 | 255 | Device Attributes |
G1 | BIN | R/W | 0 | 65535 | Binary Inputs |
G10 | BIN | R/W | 0 | 65535 | Binary Outputs |
G20 | UINT16, UINT32 | R/W | 0 | 65535 | Counters |
G30 | INT16, UINT16, INT32, UINT32, INT64, UINT64, FLT32, FLT64 | R/W | 0 | 65535 | Analog Inputs |
G40 | INT16, UINT16, INT32, UINT32, INT64, UINT64, FLT32, FLT64 | R/W | 0 | 65535 | Analog Outputs |
G50 | DNP3TIME | R/W | 0 | 65535 | Time |
G110 | OSTR | R/W | 0 | 65535 | Octet strings |
T-Params | UINT8, UINT16, UINT32, UINT64, INT8, INT16, INT32, INT64, ENUM16, FLT32, FLT64, TIME, UC10, UC20, UC30, UC40 | R/W | 0 | 0 | Tunneling: Parameters |