AB MicroLogix (Gen1)
Important: This driver was deprecated in Litmus Edge version 3.5.2. We recommend using the Gen 2 AB EthernetIP Ethernet.
Review the following information for setting up and configuring the AB MicroLogix (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Ethernet |
Validated devices/series | Rockwell Automation Allen-Bradley MicroLogix 1000 Rockwell Automation Allen-Bradley MicroLogix 1100 Rockwell Automation Allen-Bradley MicroLogix 1200 Rockwell Automation Allen-Bradley MicroLogix 1400 Rockwell Automation Allen-Bradley MicroLogix 1500 Rockwell Automation Allen-Bradley SLC 5/03 Rockwell Automation Allen-Bradley SLC 5/04 with 1761-NET-ENI Rockwell Automation Allen-Bradley SLC 5/05 Ethernet port |
Replaced with Gen 2 driver |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, use PLC software on your computer to configure the device for Ethernet access.
Refer to the following parameters.
Communication mode: Port Setting: 10/100 Mbps Full Duplex/Half Duplex
Parameter | Value |
---|---|
Type | Allen-Bradley |
Driver | AB MicroLogix (Gen1) |
Network Address | The device address you defined in Step 1 |
Port | 102 |
Slot Number | 0 |
When you Add Tags to the connected device, use the following tag/register mapping table.
Name | Value Type | Access Types | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|---|
I | bit | R/W | DDDdd | 0 | 25515 | Input bit |
O | bit | R/W | DDDdd | 0 | 25515 | Output bit |
S | bit | R/W | DDD | 0 | 255 | Status bit |
B3 | bit | R/W | DDDdd | 0 | 25515 | Bit Data file (B3) |
Bfn | bit | R/W | FFFDDDdd | 100000 | 25525515 | Bit Data File |
T4ACC | int | R/W | DDD | 0 | 255 | Timer Accumulator (T4) |
T4PRE | int | R/W | DDD | 0 | 255 | Timer Prese (T4) |
TfnACC | int | R/W | FFFDDD | 1000 | 255255 | Timer Accumulator |
Tfn_PRE | int | R/W | FFFDDD | 1000 | 255255 | Timer Preset |
CS_ACC | int | R/W | DDD | 0 | 255 | Counter Accumulator (CS) |
CS_PRE | int | R/W | DDD | 0 | 255 | Counter Preset (CS) |
Cfn_ACC | int | R/W | FFFDDD | 1000 | 255255 | Counter Accumulator |
Cfn_PRE | int | R/W | FFFDDD | 1000 | 255255 | Counter Preset |
R6 | int | R/W | DDD | 0 | 255 | Control File (R6) |
R6.POS | int | R/W | DDD | 0 | 255 | Control file pointer position (R6) |
R6.LEN | int | R/W | DDD | 0 | 255 | Control file length (R6) |
Rfn | int | R/W | FFFDDD | 0 | 255255 | Control File |
Rfn_POS | int | R/W | FFFDDD | 0 | 255255 | Control file pointer position |
Rfn_LEN | int | R/W | FFFDDD | 0 | 255255 | Control file length |
N7 | int | R/W | DDD | 0 | 255 | Integer Data File (N7) |
Nfn | int | R/W | FFFDDD | 1000 | 255999 | Integer Data File |
Lfn | int | R/W | FFFDDD | 1000 | 255999 |
|
F8 | float | R/W | DDD | 0 | 255 | Floating Point data file (F8) |
Ffn | float | R/W | FFFDDD | 1000 | 255999 | Floating Point data file |