To set up and configure this device in Litmus Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Litmus Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device



To configure your device:

1. Note down the following information and refer to it when needed.

Device: Cutler-Hammer ELC-PV28NNDR

Communication I/F: RS232, refer to the following figures.

ELC Serial (Gen1) reference [1]
ELC Serial (Gen1) reference [1]

ELC Serial (Gen1) reference [2]
ELC Serial (Gen1) reference [2]


2. Launch ELCSoft v2.07 software, Options > Communication Setting.

3. Click Communication > Transfer Setup.

4. Read from PLC to PC.

Step 2: Set up the PLC Device in Litmus Edge DeviceHub



Parameter

Value

Type

Cutler-Hammer

Driver

ELC Serial (Gen1)

Communication Port

Local Serial connection file path

Data Bits

7

Baud Rate

9600

Parity

Even, Odd, None

Stop Bits

1



Name

Value Types

Access Types

Address Format

Min Address

Max Address

C_Bit

bit

R/W

DDD

0

255

M

bit

R/W

DDDD

0

4095

S

bit

R/W

DDDD

0

1023

T_Bit

bit

R/W

DDD

0

255

X

bit

R/W

OOO

0

255

Y

bit

R/W

OOO

0

255

T

word

R/W

DDD

0

255

D

word

R/W

DDDDD

0

11999

C_32Bit

dword

R/W

DDD

200

255

C

word

R/W

DDD

0

199



/le