QuickStart Guide
...
Industrial Systems Connection ...
Delta PLC

Delta DVP (Gen1)

6min

Review the following information for setting up and configuring the Delta DVP (Gen1) driver.

Litmus Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

To set up and configure this device in Litmus Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Litmus Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, follow the steps below.

To configure your device:

  1. Note down the following information and refer to it when needed.

    Device: Delta DVP-12E

    Communication I/F: Ethernet. Refer to the following figure.

    Delta DVP reference
    Delta DVP reference
    
  2. Launch IPSoft V3.06 software, and then open a new project.
  3. Search for the device.
  4. Click the device, click the Basic tab, and set up the network parameters.

    Network parameters
    Network parameters
    
  5. Launch COMMGR and configure the driver.
  6. Click Tool > Communication Setting, select the driver, and then click Connect.

    Connect option
    Connect option
    

Step 2: Set up the PLC Device in Litmus Edge DeviceHub



Parameter

Value

Type

Delta PLC

Driver

Delta DVP (Gen1)

Network Address

The device address you defined in Step 1

Port

502



Name

Value Types

Access Types

Address Format



Min Address

Max Address

C_Bit

bit

R/W

DDD



0

255

M

bit

R/W

DDDD



0

4095

S

bit

R/W

DDDD



0

1023

T_Bit

bit

R/W

DDD



0

255

X

bit

R/W

OOO



0

571

Y

bit

R/W

OOO



0

571

T

word

R/W

DDD



0

255

D

word

R/W

DDDDD



0

11999

C_32Bit

word

R/W

DDD



200

255

C

word

R/W

DDD



0

199