GE Fanuc RX3i Serial (Gen1.3)
4 min
review the following information for setting up and configuring the ge fanuc rx3i serial (gen1 3) driver litmus edge compatible series compatibility parameter compatible items driver type serial validated devices/series ge fanuc rx3i series to set up and configure this device in litmus edge, you will need to do the following step 1 set up and configure the plc device step 2 set up the plc device in litmus edge devicehub step 3 configure the list of registers step 1 set up and configure the plc device to configure your device note down the following information and refer to it when needed device ge fanuc rx3i communication i/f rs232, refer to the following figure launch proficy machine edition v8 0 software to configure the device for ethernet access step 2 set up the plc device in litmus edge devicehub parameter value type ge fanuc driver ge fanuc rx3i serial (gen1 3) communication port local serial connection file path baud rate 19200 data bits 8 parity even, odd, none stop bits 1 station id 1 name value type access types address format min address max address description i bit r/w ddddd 1 32768 input bit q bit r/w ddddd 1 32768 output bit m bit r/w ddddd 1 32768 g bit r/w dddd 1 7680 t bit r/w dddd 1 1024 sa bit r/w ddd 1 128 sb bit r/w ddd 1 128 sc bit r/w ddd 1 128 s bit r/w ddd 1 25471 r word r/w ddddd 1 32640 aq word r/w ddddd 1 32640 analog output ai word r/w ddddd 1 32640 analog input