QuickStart Guide
...
Industrial Systems Connection ...
GE Fanuc

GE Fanuc SNP Serial (Gen1)

6min

Review the following information for setting up and configuring the GE Fanuc SNP Serial (Gen1) driver.

Litmus Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Serial

Validated devices/series

GE Fanuc VersaMax

To set up and configure this device in Litmus Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Litmus Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device



To configure your device:

  1. Note down the following information and refer to it when needed.

    Device: GE Fanuc VersaMax Microax Micro, IC200UDR064

    Communication I/F: RS232. Refer to the following figure.

    GE Fanuc SNP Serial reference
    GE Fanuc SNP Serial reference
    
  2. Launch Proficy Machine Edition v.80 software, and then select the COM port.
  3. Click Target > Go Online with Target1.

Step 2: Set up the PLC Device in Litmus Edge DeviceHub



Parameter

Value

Type

GE Fanuc

Driver

GE Fanuc SNP Serial (Gen1)

Communication Port

Local Serial connection file path

Baud Rate

19200

Data Bits

8

Parity

Even, Odd, None

Stop Bits

1

Station

1



Name

Value Types

Access Types

Address Format

Min Address

Max Address

Description

I

bit

R/W

DDDDD

1

10000

Input Relay

Q

bit

R/W

DDDDD

1

10000

Output Relay

M

bit

R/W

DDDDD

1

10000

Auxiliary Relay

G

bit

R/W

DDDD

1

7680

 

T

bit

R/W

DDD

1

256

 

SA

bit

R/W

DDD

1

128

 

SB

bit

R/W

DDD

1

128

 

SC

bit

R/W

DDD

1

128

 

S

bit

R/W

DDD

1

128

 

R_Bit

bit

R/W

DDDDDdd

100

3264015

Data Register bit

R

word

R/W

DDDDD

1

32640

Data Register

AQ

word

R/W

DDDDD

1

10000

Analog output register

AI

word

R/W

DDDDD

1

10000

Analog input register