Mitsubishi A2SH Serial (Gen1)
Note: This driver will be deprecated in a future Litmus Edge release. We recommend using the Gen 2 Mitsubishi A Series Serial.
Review the following information for setting up and configuring the Mitsubishi A2SH Serial (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Serial |
Validated devices/series | A Series models:
|
Replaced with Gen 2 driver |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
To configure your device:
Note down the following information and refer to it when needed. Device: Mitsubishi A3A/A3N/A1SH/A2SH Communication I/F: RS232 with a serial cable. Refer to the following figure.
- Launch GX developer v8.103 software and connect the device with a serial cable.
Click Online > Read from PLC.
Select the PLC series.
Set up communications, and then click Communication Test.
Parameter | Value |
---|---|
Type | Mitsubishi |
Driver | Mitsubishi A2SH Serial (Gen1) |
Communication Port | Local Serial connection file path |
Data Bits | 8 |
Baud Rate | 9600 |
Parity | Even, Odd, None |
Stop Bits | 1 |
Name | Value Types | Access Types | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|---|
X | bit | R/W | HHHH | 0 | 65535 | Input Relay |
Y | bit | R/W | HHHH | 0 | 65535 | Output Relay |
M | bit | R/W | DDDDD | 0 | 65535 | Auxiliary Relay |
B | bit | R/W | HHHH | 0 | 65535 |
|
F | bit | R/W | DDDDD | 0 | 65535 |
|
R | word | R/W | DDDDD | 0 | 65535 |
|
W | word | R/W | HHHH | 0 | 65535 |
|
D | word | R/W | DDDDD | 0 | 65535 | Data Register |
CV | word | R/W | DDDDD | 0 | 65535 | Counter Memory |
TV | word | R/W | DDDDD | 0 | 65535 | Timer Memory |