Mitsubishi FX2N Serial (Gen1)
Review the following information for setting up and configuring the Mitsubishi FX2N Serial (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Serial |
Validated devices/series | MELSEC-F |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
Parameter | Value |
---|---|
Type | Mitsubishi |
Driver | Mitsubishi FX2N Serial (Gen1) |
Communication Port | Local Serial connection file path |
Data Bits | 8 |
Baud Rate | 9600 |
Parity | Even, Odd, None |
Stop Bits | 1 |
Name | Value Type | | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|---|
X | bit | R/W | OOO | 0 | 255 | Input Relay |
Y | bit | R/W | OOO | 0 | 255 | Output Relay |
M | bit | R/W | DDDD | 0 | 7999 | Auxiliary Relay |
T | bit | R/W | DDD | 0 | 511 | Timer Relay |
C | bit | R/W | DDD | 0 | 255 | Counter Relay |
SM | bit | R/W | DDDD | 8000 | 8511 | Special Auxiliary Relay |
S | bit | R/W | DDDD | 0 | 4095 | State Relay (5) |
D_Bit | bit | R/W | DDDDdd | 0 | 799915 | Data Register Bit (D) |
SD | word | R/W | DDDD | 8000 | 8511 | Special Data Register |
CV2 | word | R/W | DDD | 200 | 255 | Counter Memory (D Word) |
D | word | R/W | DDDD | 0 | 7999 | Data Register |
CV | word | R/W | DDD | 0 | 199 | Counter Memory |
TV | word | R/W | DDD | 0 | 511 | Timer Memory |