Modbus TCP
Review the following information for setting up and configuring the Modbus TCP driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Ethernet |
When to use | TCP connection to a Modbus device |
Replaces Gen 1 driver(s) | Learn more about Gen1 and Gen2 Driver Differences |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
Parameter | Value |
---|---|
Type | Modbus |
Driver | Modbus TCP |
Network Address | The device address you defined in Step 1 |
Network Port | 502 |
Station ID | 0 |
Zero-Based Addressing | Select Enable or Disable |
Note: The address format in this Gen 2 driver is different from the Gen 1 driver (Modbus TCP (Gen1)) for the same device. Learn more about Gen1 and Gen2 Driver Differences.
Name | Value Types | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|
D | bit | DDDDD | 0 | 65535 | Discrete Input Contacts |
C | bit | DDDDD | 0 | 65535 | Discrete Output Coils |
H | word, int16, int32, uint32, float32, float64 | DDDDD | 0 | 65535 | Analog Output Holding Registers |
I | word, int16, int32, uint32, float32, float64 | DDDDD | 0 | 65535 | Analog Input Registers |
H_bit | bit | DDDDDdd | 0 | 65535 | Analog Output Holding Registers |
I_bit | bit | DDDDDdd | 0 | 65535 | Analog Input Registers |