Omron Fins Ethernet (Gen1)
Review the following information for setting up and configuring the Omron Fins Ethernet (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Ethernet |
Validated devices/series | |
Replaced with Gen 2 driver |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, follow the steps below.
To configure your device:
Note down the following information and refer to it as needed.
- Connect the PC to the device using USB cable.
- Launch CX Programmer and create a project.
- Click PLC > Work Online.
- Open IO Table and Unit Setting and create IO table based on hardware allocation.
- Set up communication Parameters for communication module.
- Transfer to PLC.
- Log in using Ethernet, click Offline, and then click the device name.
- Select Ethernet as the network type, click Settings, set up the IP and Port number, and then click PLC > Work Online.
Parameter | Value |
---|---|
Type | Omron |
Driver | Omron Fins Ethernet (Gen1) |
Network Address | The device address you defined during Step 1 |
Port | 9600 |
Name | Value Types | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|
CIO_bit | bit | DDDDDdd | 0 | 3276715 | Channel I/O bit |
CIO | word, string | DDDDD | 0 | 32767 | Channel I/O |
W | word, string | DDDDD | 0 | 32767 | Work Area |
A | word, string | DDDDD | 0 | 32767 | Auxiliary Relay |
H | word, string | DDDDD | 0 | 32767 | Holding Area |
C | word, string | DDDDD | 0 | 32767 | Counter |
T | word, string | DDDDD | 0 | 32767 | Timer |
D | word, string | DDDDD | 0 | 32767 | Data Memory |
EM0 | word, string | DDDDD | 0 | 32767 | Extended Memory |
EM1 | word, string | DDDDD | 0 | 32767 | Extended Memory |
EM2 | word, string | DDDDD | 0 | 32767 | Extended Memory |
EM3 | word, string | DDDDD | 0 | 32767 | Extended Memory |