Review the following information for setting up and configuring the Siemens S7-300 Serial (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Serial |
Validated devices/series | S7-300 |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
Parameter | Value |
---|---|
Type | Siemens |
Driver | Siemens S7-300 Serial (Gen1) |
Communication Port | Local Serial connection file path |
Baud Rate | 19200 |
Data Bits | 8 |
Parity | Even, Odd, None |
Stop Bits | 1 |
Station | 2 |
Name | Value Type | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|
PE | bit, word | DDDDd | 0 | 40957 | |
PA | bit, word | DDDDd | 0 | 40957 | |
MK | bit, byte, word, dword, real, counter, timer | DDDDd | 0 | 40957 | |
DB | bit, byte, sint, word, int, stime, time, date, time_of_day, char, dword, dint, real, string | DDDDDd | 0 | 327677 | Data Block |