QuickStart Guide
...
Industrial Systems Connection ...
Toshiba

Toshiba Computer Link Ethernet (Gen1)

5min

Review the following information for setting up and configuring the Toshiba Computer Link Ethernet (Gen1) driver.

Litmus Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

Any of the following Toshiba series models with an Ethernet module:

  • S2
  • S3
  • T2
  • T3

To set up and configure this device in Litmus Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Litmus Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, use PLC software on your computer to configure your device for Ethernet access.

Step 2: Set up the PLC Device in Litmus Edge DeviceHub



Parameter

Value

Type

Toshiba

Driver

Toshiba Computer Link Ethernet (Gen1)

Network Address

The device address you defined in Step 1

Network Port

1024



Name

Value Types

Address Format

Min Address

Max Address

Description

X

bit

DDDDdd

0

511915

Input Devices

I

bit

DDDDdd

0

511915

Direct Input Devices

Y

bit

DDDDdd

0

511915

Output Devices

O

bit

DDDDdd

0

511915

Direct Output Devices

R

bit

DDDDdd

0

409515

Auxiliary Devices

DBit

bit

DDDDdd

0

409515

Auxiliary Devices

S

bit

DDDdd

0

51115

Special Devices

XW

word,short,dword,long,float

DDDD

0

5119

Input Registers

IW

word,short,dword,long,float

DDDD

0

5119

Direct Input Registers

YW

word,short,dword,long,float

DDDD

0

5119

Output Registers

OW

word,short,dword,long,float

DDDD

0

5119

Direct Output Registers

RW

word,short,dword,long,float

DDDD

0

4095

Auxiliary Registers

DW

word,short,dword,long,float

DDDD

0

5119

Auxiliary Registers

SW

word,short,dword,long,float

DDD

0

511

Special Registers

D

word,short,dword,long,float

DDDD

0

4095

Data Memory

DH

string

DDDD

0

4095

Data Memory As String with HiLo Byte Order

DL

string

DDDD

0

4095

Data Memory As String with LoHi Byte Order