IEC60870-5-102 Ethernet (Gen1)
Review the following information for setting up and configuring the IEC60870-5-102 Ethernet (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Ethernet |
Device standard | IEC 60870-5-102 |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, use software on your computer to configure the device for Ethernet access.
Parameter | Value |
---|---|
Type | IEC |
Driver | IEC60870-5-102 Ethernet (Gen1) |
Network Address | The device address you defined in Step 1 |
Network Port | 2404 |
Asdu Addr Size | 2 |
Link Address | 3 |
Name | Value Types | Access Types | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|---|
M_SP_TA_2 | bit | R/W | DDDddd | 0 | 255999 | Single point information |
M_IT_TA_2 | word | R/W | DDDddd | 0 | 255999 | Accounting integrated totals, four octets each |
M_IT_TB_2 | word | R/W | DDDddd | 0 | 255999 | Accounting integrated totals, three octets each |
M_IT_TC_2 | word | R/W | DDDddd | 0 | 255999 | Accounting integrated totals, two octets each |
M_IT_TD_2 | word | R/W | DDDddd | 0 | 255999 | Periodically Reset Accounting integrated totals, four octets each |
M_IT_TE_2 | word | R/W | DDDddd | 0 | 255999 | Periodically Reset Accounting integrated totals, three octets each |
M_IT_TF_2 | word | R/W | DDDddd | 0 | 255999 | Periodically Reset Accounting integrated totals, two octets each |
M_IT_TG_2 | word | R/W | DDDddd | 0 | 255999 | Operational integrated totals, four octets each |
M_IT_TH_2 | word | R/W | DDDddd | 0 | 255999 | Operational integrated totals, three octets each |
M_IT_TI_2 | word | R/W | DDDddd | 0 | 255999 | Operational integrated totals, two octets each |
M_IT_TK_2 | word | R/W | DDDddd | 0 | 255999 | Periodically Reset Operational integrated totals, four octets each |
M_IT_TL_2 | word | R/W | DDDddd | 0 | 255999 | Periodically Reset Operational integrated totals, three octets each |
M_IT_TM_2 | word | R/W | DDDddd | 0 | 255999 | Periodically Reset Operational integrated totals, two octets each |
C_RD_NA_2 | custom | R/W | D | 1 | 1 | Read manufacture and product specification |
C_TI_NA_2 | custom | R/W | D | 1 | 1 | Read current system time of integrated total DTE |
C_SP_NA_2 | custom | R/W | DDD | 0 | 255 | Read record of single-point information with time tag |
C_SP_NB_2 | custom | R/W | DDD | 0 | 255 | Read record of single-point information with time tag of a selected time range |
C_CI_NA_2 | custom | R/W | DDD | 0 | 255 | Read accounting integrated totals of the oldest integration period |
C_CI_NE_2 | custom | R/W | DDD | 0 | 255 | Read periodically reset accounting integrated totals of the oldest integration period |
C_CI_NI_2 | custom | R/W | DDD | 0 | 255 | Read operational integrated totals of the oldest integration period |
C_CI_NN_2 | custom | R/W | DDD | 0 | 255 | Read periodically reset operational integrated totals of the oldest integration period |
C_CI_NB_2 | custom | R/W | DDDSSSEEE | 0 | 255255255 | Read accounting integrated totals of the oldest integration period and of a selected range of addresses |
C_CI_NF_2 | custom | R/W | DDDSSSEEE | 0 | 255255255 | Read periodically reset accounting integrated totals of the oldest integration period and of a selected range of addresses |
C_CI_NK_2 | custom | R/W | DDDSSSEEE | 0 | 255255255 | Read operational integrated totals of the oldest integration period and of a selected range of addresses |
C_CI_NO_2 | custom | R/W | DDDSSSEEE | 0 | 255255255 | Read periodically reset operational integrated totals of the oldest integration period and of a selected range of addresses |
C_CI_NR_2 | custom | R/W | DDDSSSEEE | 0 | 255255255 | Read accounting integrated totals of a selected time range and of a selected range of addresses |
C_CI_NS_2 | custom | R/W | DDDSSSEEE | 0 | 255255255 | Read periodically reset accounting integrated totals of a selected time range and of a selected range of addresses |
C_CI_NT_2 | custom | R/W | DDDSSSEEE | 0 | 255255255 | Read operational integrated totals of a selected time range and of a selected range of addresses |
C_CI_NU_2 | custom | R/W | DDDSSSEEE | 0 | 255255255 | Read periodically reset operational integrated totals of a selected time range and of a selected range of addresses |