QuickStart Guide
...
Industrial Systems Connection ...
IEC

IEC60870-5-102 Ethernet (Gen1)

5min

Review the following information for setting up and configuring the IEC60870-5-102 Ethernet (Gen1) driver.

Litmus Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Device standard

IEC 60870-5-102

To set up and configure this device in Litmus Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Litmus Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, use software on your computer to configure the device for Ethernet access.

Step 2: Set up the PLC Device in Litmus Edge DeviceHub



Parameter

Value

Type

IEC

Driver

IEC60870-5-102 Ethernet (Gen1)

Network Address

The device address you defined in Step 1

Network Port

2404

Asdu Addr Size

2

Link Address

3



Name

Value Types

Access Types

Address Format

Min Address

Max Address

Description

M_SP_TA_2

bit

R/W

DDDddd

0

255999

Single point information

M_IT_TA_2

word

R/W

DDDddd

0

255999

Accounting integrated totals, four octets each

M_IT_TB_2

word

R/W

DDDddd

0

255999

Accounting integrated totals, three octets each

M_IT_TC_2

word

R/W

DDDddd

0

255999

Accounting integrated totals, two octets each

M_IT_TD_2

word

R/W

DDDddd

0

255999

Periodically Reset Accounting integrated totals, four octets each

M_IT_TE_2

word

R/W

DDDddd

0

255999

Periodically Reset Accounting integrated totals, three octets each

M_IT_TF_2

word

R/W

DDDddd

0

255999

Periodically Reset Accounting integrated totals, two octets each

M_IT_TG_2

word

R/W

DDDddd

0

255999

Operational integrated totals, four octets each

M_IT_TH_2

word

R/W

DDDddd

0

255999

Operational integrated totals, three octets each

M_IT_TI_2

word

R/W

DDDddd

0

255999

Operational integrated totals, two octets each

M_IT_TK_2

word

R/W

DDDddd

0

255999

Periodically Reset Operational integrated totals, four octets each

M_IT_TL_2

word

R/W

DDDddd

0

255999

Periodically Reset Operational integrated totals, three octets each

M_IT_TM_2

word

R/W

DDDddd

0

255999

Periodically Reset Operational integrated totals, two octets each

C_RD_NA_2

custom

R/W

D

1

1

Read manufacture and product specification

C_TI_NA_2

custom

R/W

D

1

1

Read current system time of integrated total DTE

C_SP_NA_2

custom

R/W

DDD

0

255

Read record of single-point information with time tag

C_SP_NB_2

custom

R/W

DDD

0

255

Read record of single-point information with time tag of a selected time range

C_CI_NA_2

custom

R/W

DDD

0

255

Read accounting integrated totals of the oldest integration period

C_CI_NE_2

custom

R/W

DDD

0

255

Read periodically reset accounting integrated totals of the oldest integration period

C_CI_NI_2

custom

R/W

DDD

0

255

Read operational integrated totals of the oldest integration period

C_CI_NN_2

custom

R/W

DDD

0

255

Read periodically reset operational integrated totals of the oldest integration period

C_CI_NB_2

custom

R/W

DDDSSSEEE

0

255255255

Read accounting integrated totals of the oldest integration period and of a selected range of addresses

C_CI_NF_2

custom

R/W

DDDSSSEEE

0

255255255

Read periodically reset accounting integrated totals of the oldest integration period and of a selected range of addresses

C_CI_NK_2

custom

R/W

DDDSSSEEE

0

255255255

Read operational integrated totals of the oldest integration period and of a selected range of addresses

C_CI_NO_2

custom

R/W

DDDSSSEEE

0

255255255

Read periodically reset operational integrated totals of the oldest integration period and of a selected range of addresses

C_CI_NR_2

custom

R/W

DDDSSSEEE

0

255255255

Read accounting integrated totals of a selected time range and of a selected range of addresses

C_CI_NS_2

custom

R/W

DDDSSSEEE

0

255255255

Read periodically reset accounting integrated totals of a selected time range and of a selected range of addresses

C_CI_NT_2

custom

R/W

DDDSSSEEE

0

255255255

Read operational integrated totals of a selected time range and of a selected range of addresses

C_CI_NU_2

custom

R/W

DDDSSSEEE

0

255255255

Read periodically reset operational integrated totals of a selected time range and of a selected range of addresses