DNP3 Ethernet
Review the following information for setting up and configuring the DNP3 Ethernet driver.
Notes:
- This driver does not support File Transfer or SAv5.
- This driver supports Emerson's DNP3 tunneling method for Emerson FBx RTUs only.
Compatibility parameter | Compatible items |
---|---|
Driver type | Ethernet |
Validated devices/series |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, use software on your computer to configure the device for Ethernet access.
Caution: Make sure that the value you enter for Master Address is unique.
Parameter | Value |
---|---|
Type | Emerson |
Driver | DNP3 Ethernet |
Network Address | The device address you defined in Step 1 |
Network Port | 20000 |
Outstation Address | 1 |
Master Address | 0 |
Class 1 Poll Interval | 5 |
Class 2 Poll Interval | 5 |
Class 3 Poll Interval | 5 |
Name | Value Types | Access Types | Min Address | Max Address | Description |
---|---|---|---|---|---|
G0 | ATTRIBUTE | R/W | 0 | 1023 | Device Attributes |
G1 | BIN | R/W | 0 | 1023 | Binary Input |
G10 | BIN | R/W | 0 | 1023 | Binary Output Status |
G20 | UINT16, UINT32 | R/W | 0 | 1023 | Counter |
G30 | FLT 32, FLT64, INT16, INT32 | R/W | 0 | 65535 | Analog Input |
G40 | FLT 32, FLT64, INT16, INT32 | R/W | 0 | 65535 | Analog Output Status |
G50 | DNP3TIME | R/W | 0 | 65535 | Time |
G110 | OSTR | R/W | 0 | 65535 | Octet strings |
T-Params | UINT8, UINT16, UINT32, UINT64, INT8, INT16, INT32, INT64, FLT32, FLT64, UC10, UC20, UC30, UC40, ENUM16, TIME | R/W | 0 | 65535 | Tunneling: Parameters |