QuickStart Guide
...
Industrial Systems Connection ...
Emerson

DNP3 Ethernet with FB Extensions

6min

Review the following information for setting up and configuring the DNP3 Ethernet with FB Extensions driver.

Notes:

  • This driver does not support SAv5.
  • This driver supports Emerson's DNP3 tunneling method for Emerson FBx RTUs only.

Litmus Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

To set up and configure this device in Litmus Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Litmus Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, use software on your computer to configure the device for Ethernet access.

Step 2: Set up the PLC Device in Litmus Edge DeviceHub



Caution: Make sure that the value you enter for Master Address is unique.

Parameter

Value

Type

Emerson

Driver

DNP3 Ethernet with FB Extensions

Network Address

The device address you defined in Step 1

Network Port

20000

Outstation Address

The outstation address defined in the device configuration.

Master Address

0

Class 1/2/3 Poll Period

The default value is 30, but you can customize it to your requirements.



Name

Value Types

Access Types

Min Address

Max Address

Access Type

Description

G0

ATTRIBUTE

R/W

0

255

R/W

Device Attributes

G1

BIN

R/W

0

65535

R/W

Binary Inputs

G10

BIN

R/W

0

65535

R/W

Binary Outputs

G20

UINT16, UINT32

R/W

0

65535

R/W

Counters

G30

INT16, UINT16, INT32, UINT32, INT64, UINT64, FLT32, FLT64

R/W

0

65535

R/W

Analog Inputs

G40

INT16, UINT16, INT32, UINT32, INT64, UINT64, FLT32, FLT64

R/W

0

65535

R/W

Analog Outputs

G50

DNP3TIME

R/W

0

65535

R/W

Time

G70

FILE

R/W

0

65535

R/W

File Control

G110

OSTR

R/W

0

65535

R/W

Octet strings

T-Params

UINT8, UINT16, UINT32, UINT64, INT8, INT16, INT32, INT64, ENUM16, FLT32, FLT64, TIME, UC10, UC20, UC30, UC40

R/W

0

65535

R/W

Tunneling: Parameters