Mitsubishi FX5U-Ethernet ASCII (Gen1)
Review the following information for setting up and configuring the Mitsubishi FX5U-Ethernet ASCII (Gen1) driver.
Compatibility parameter | Compatible items |
Driver type | Ethernet |
Validated devices/series |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, follow the steps below.
To configure your device:
Note down the following information and refer to it when needed.
Launch GXWork3 V1.035M software, and then click Online > Read from PLC.
Select the series.
Select the connection destination.
Double-click the PLC module icon, and click Find to browse the device on the network.
- From the Navigation panel, click Ethernet Port to set up communication parameters. Use ASCII for this device.
Double-click External Device Configuration.
Set up the connections. In this case, port 4996 through 4999 are able to connect.
Parameter | Value |
Type | Mitsubishi |
Driver | Mitsubishi FX5U-Ethernet-ASCII (Gen1) |
Network Address | The device address you defined in Step 1 |
Port | 5002 |
Station ID | 255 |
Name | Value Type | Address Format | Min Address | Max Address | Description |
SM | bit | DDDD | 0 | 9999 | Special Relay |
X | bit | HHHH | 0 | 1023 | Input Relay |
Y | bit | HHHH | 0 | 1023 | Output Relay |
M | bit | DDDDD | 0 | 65535 | Internal Relay |
L | bit | DDDDD | 0 | 32237 | Latch Relay |
F | bit | DDDDD | 0 | 32237 | Annunciator |
B | bit | DDDDD | 0 | 32237 | Link Relay |
TS | bit | DDDD | 0 | 1023 | Timer Contact |
TC | bit | DDDD | 0 | 1023 | Timer Coil |
CS | bit | DDDD | 0 | 1023 | Counter Contact |
CC | bit | DDDD | 0 | 1023 | Counter Coil |
SB | bit | DDDDD | 0 | 32737 | Special Link Relay |
S | bit | DDDD | 0 | 4095 | Step Relay |
Z | word | DD | 0 | 19 | Index Register |
SW | word | DDDDD | 0 | 32767 | Special Link Register |
CN | word | DDDD | 0 | 1023 | Counter Current Value |
SN | word | DDDD | 0 | 1023 | Retentive Timer Current Value |
TN | word | DDDD | 0 | 1023 | Timer current Value |
W | word | DDDDD | 0 | 32767 | Link Register |
R | word | DDDDD | 0 | 32767 | File Register |
D | word | DDDD | 0 | 7999 | Data Register |
SD | word | DDDDD | 0 | 11999 | Special Register |
LZ | word | D | 0 | 1 | Long Index Register |