QuickStart Guide
...
Mitsubishi
Gen 1 Drivers

Mitsubishi SLMP (Gen1)

6min

Review the following information for setting up and configuring the Mitsubishi SLMP (Gen1) driver.

Litmus Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

To set up and configure this device in Litmus Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Litmus Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, use PLC software on your computer to configure the device for Ethernet access.

Note: Only one connection is allowed per port defined in the PLC.

Step 2: Set up the PLC Device in Litmus Edge DeviceHub



Parameter

Value

Type

Mitsubishi

Driver

Mitsubishi SLMP (Gen1)

Network Address

The device address you defined in Step 1

Port

1025

Station ID

255



Name

Value Type

Address Format

Min Address

Max Address

Description

X

bit

HHHh

0

12287

Input

Y

bit

HHHh

0

12287

Output

M

bit

DDDDDDDD

0

16777215

Internal Relay

L

bit

DDDDD

0

32767

Latch Relay

B

bit

HHHHHHHh

0

268435455

Link Relay

F

bit

DDDDD

0

32767

Annunciator

S

bit

DDDD

0

4095

 

SB

bit

HHHHHHh

0

268435455

Link Special Relay

V

bit

DDDDD

0

32767

Edge Relay

DX

bit

HHHH

0

8191

 

DY

bit

HHHH

0

8191

 

TS

bit

DDDDDDD

0

8993439

Timer Contact

TC

bit

DDDDDDD

0

08993439

Timer Coil

SS

bit

DDDDDDD

0

8993439

Retentive Timer

SC

bit

DDDDDDD

0

8993439

Retentive Timer Coil

CS

bit

DDDDDDD

0

8993439

Counter Contact

CC

bit

DDDDDDD

0

8993439

Counter Coil

SM

bit

DDDD

0

4095

Special Relay

TN

word

DDDDDDD

0

8993439

Timer Current Value

SN

word

DDDDDDD

0

8993439

Retentive Timer Current

CN

word

DDDDDDD

0

8993439

Counter Current Value

D

word

DDDDDDDD

0

10117631

Data Register

W

word

HHHHHH

0

10117631

Link Register

SW

word

HHHHHH

0

10117631

Special Link Register

SD

word

DDDD

0

4095

Special Register

Z

word

DD

0

23

Index Register

R

word

DDDDD

0

32767

File Register

ZR

word

HHH

0

65535

File Register