Mitsubishi R04-Ethernet-Binary (Gen1)
Review the following information for setting up and configuring the Mitsubishi R04-Ethernet-Binary (Gen1) driver.
Compatibility parameter | Compatible items |
Driver type | Ethernet |
Validated devices/series |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, follow the steps below.
To configure your device:
- Note down the following information and refer to it when needed. Device: Mitsubishi R04CPU Communication I/F: Ethernet
- Connect the device to your PC using a USB.
- Launch GXWorks 3 v1.035M software.
- From the navigation panel, navigate to System Parameters > Read Mounting status, and then check for the CPU to display.
- From the navigation panel, click Module Configuration to see if the base rack and CPU display.
- Click Module Parameters and enter the desired IP Address, Subnet Mask, and Default Gateway.
- If you want to write back to PLC tags with Litmus Edge, make sure the Enable/Disable Online Change setting is set to Enable All (SLMP).
- Click External Device Configuration (Detailed Setting) to set up the connection (Ethernet Built-in port).
- Draw SLMP Connection Module from the Module list to the left.
- Set up of the port number depends on how many devices need to connect with the PLC.
- Click Close with Reflecting the Setting, click Apply, and then click Write to PLC.
- Power the PLC off and on again to activate the setting.
- From the navigation panel, navigate to Connection Destination > connection, click Find CPU (Built-in Ethernet port) on Network, and then select the target device.
- Click Connection Test.
Parameter | Value |
Type | Mitsubishi |
Driver | Mitsubishi R04-Ethernet-Binary (Gen1) |
Network Address | The device address you defined in Step 1 |
Port | 5007 |
Station ID | 255 |
Name | Value Types | Address Format | Min Address | Max Address | Description |
X | bit | HHHh | 0 | 12287 | Input |
Y | bit | HHHh | 0 | 12287 | Output |
M | bit | DDDDDDDD | 0 | 16777215 | Internal Relay |
L | bit | DDDDD | 0 | 32767 | Latch Relay |
B | bit | HHHHHHh | 0 | 268435455 | Link Relay |
F | bit | DDDDD | 0 | 32767 | Annunciator |
SB | bit | HHHHHHh | 0 | 268435455 | Link Special Relay |
V | bit | DDDDD | 0 | 32767 | Edge Relay |
TS | bit | DDDDDDD | 0 | 8993439 | Timer Contact |
TC | bit | DDDDDDD | 0 | 8493439 | Timer Coil |
SS | bit | DDDDDDD | 0 | 8993439 | Retentive Timer |
SC | bit | DDDDDDD | 0 | 8993439 | Retentive Timer Coil |
CS | bit | DDDDDDD | 0 | 8993439 | Counter Contact |
CC | bit | DDDDDDD | 0 | 8993439 | Counter Coil |
SM | bit | DDDD | 0 | 4095 | Special Relay |
TN | word | DDDDDDD | 0 | 8993439 | Timer Current Value |
SN | word | DDDDDDD | 0 | 8993439 | Retentive Timer Current |
CN | word | DDDDDDD | 0 | 8993439 | Counter Current Value |
D | word | DDDDDDDD | 0 | 10117631 | Data Register |
W | word | HHHHHH | 0 | 10117631 | Link Register |
SW | word | HHHHHH | 0 | 10117631 | Special Link Register |
SD | word | DDDD | 0 | 4095 | Special Register |
Z | word | DD | 0 | 23 | Index Register |
R | word | DDDDD | 0 | 32767 | File Register |
ZR | word | HHHH | 0 | 65535 | File Register |