Siemens S7-1500 (Gen1)
Important: This driver was deprecated in Litmus Edge version 3.5.2. We recommend using the Gen 2 Siemens S7 or Siemens S7-Advanced (Gen1).
Review the following information for setting up and configuring the Siemens S7-1500 (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Ethernet |
Validated devices/series |
To set up and configure this device in Litmus Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Litmus Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, use PLC software on your computer to configure your device for Ethernet access.
Parameter | Value |
---|---|
Type | Siemens |
Driver | Siemens S7-1500 (Gen1) |
Network Address | The device address you defined in Step 1 |
Port | 102 |
Slot | 1 |
When you Add Tags to the connected device, use the following tag/register mapping table.
Name | Value Type | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|
PE | bit | DDDDd | 0 | 40957 |
|
PE | word | DDDD | 0 | 4095 |
|
PA | bit | DDDDd | 0 | 40957 |
|
PA | word | DDDD | 0 | 4095 |
|
MK | bit | DDDDd | 0 | 40957 |
|
MK | byte, word, dword, real, cou | DDDD | 0 | 4095 |
|
DB | bit | DDDDDd | 0 | 327677 |
|
DB | byte, sint, word, int, counter | DDDDD | 0 | 32767 |
|
S7-1500 Data Type | Data Format | Description |
---|---|---|
Byte | 8-bit BCD, Hex, Binary, Unsigned | 8-bit |
SInt | 8-bit BCD, Hex, Binary, Signed | 8-bit |
Bool | bit | bit |
USInt | 8-bit BCD, Hex, Binary, Unsigned | 8-bit |
Word | 16-bit BCD, Hex, Binary, Unsigned | 16-bit |
Int | 16-bit BCD, Hex, Binary, Signed | 16-bit |
UInt | 16-bit BCD, Hex, Binary, Unsigned | 16-bit |
DWord | 32-bit BCD, Hex, Binary, Unsigned | 32-bit |
DInt | 32-bit BCD, Hex, Binary, Signed | 32-bit |
Real | 32-bit Float | 32-bit |
UDInt | 32-bit BCD, Hex, Binary, Unsigned | 32-bit |
Array |
|
|