QuickStart Guide
...
Industrial Systems Connection ...
LS Industrial System

LS XBM Serial (Gen1)

6min

Review the following information for setting up and configuring the LS XBM Serial (Gen1) driver.

Litmus Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Serial

Validated devices/series

LS Electric XBM LS Electric XBC LS Electric XGK

To set up and configure this device in Litmus Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Litmus Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device



To configure your device:

  1. Note down the following information and refer to it when needed.

    Device: LS XBM-DR165

    Communication I/F: RS232. Refer to the following figure.

    LS XBM Serial reference
    LS XBM Serial reference
    
  2. Launch XG5000 v.3.71 software and click Online > Online Settings.
  3. Set up COM port, and then click Auto Detect.

Step 2: Set up the PLC Device in Litmus Edge DeviceHub



Parameter

Value

Type

LS Industrial System

Driver

LS XBM Serial (Gen1)

Communication Port

Local Serial connection file path

Data Bits

8

Baud Rate

115200

Parity

Even, Odd, None

Stop Bits

1



Name

Value Types



Address Format

Min Address

Max Address

Description

PW_bit

bit

R/W

DDDDdd

0

204715

I/O device bit

MW_Bit

bit

R/W

DDDDdd

0

204715

Internal device bit

LW_Bit

bit

R/W

DDDDDdd

0

1126316

Communication device bit

KW_Bit

bit

R/W

DDDDdd

0

255915

Preservation device bit

FW_Bit

bit

R/W

DDDDdd

0

204715

Special device bit

DW_Bit

bit

R/W

DDDDDdd

0

3276715

Data register bit

UW_Bit

bit

R/W

DDDDdd

0

633115

 

RW_Bit

bit

R/W

DDDDDdd

0

3276715

 

SX

bit

R/W

DDDDD

0

12799

Relay for step control bit

TX

bit

R/W

DDDD

0

2047

Timer device bit

CX

bit

R/W

DDDD

0

2047

Counter device bit

PW

word

R/W

DDDD

0

2047

I/O device

MW

word

R/W

DDDD

0

2047

Internal device

LW

word

R/W

DDDDD

0

11263

Communication device

KW

word

R/W

DDDD

0

2559

Preservation device

FW

word

R/W

DDDD

0

2047

Special device

SW

word

R/W

DDD

0

127

Relay for step control

DW

word

R/W

DDDDD

0

32767

Data register

UW

word

R/W

DDDD

0

6331

Analog data register

NW

word

R/W

DDDDD

0

21503

Communiction data register

ZW

word

R/W

DDD

0

127

Index register

TW

word

R/W

DDDD

0

2047

Timer current value

CW

word

R/W

DDDD

0

2047

Counter current value

RW

word

R/W

DDDDD

0

32767

 

ZRW

word

R/W

DDDDD

0

32767

 

TSW

word

R/W

DDDD

0

2047

Setup value

CSW

word

R/W

DDDD

0

2047

Setup value